Building maintenance and CMMS (Mindcat Maintain)

UAE

Chiller report says checked OK: what should it show, and when is it enough?

By Shivanath DevinarayananPublished 10 min read
Written forOperations or sales lead at a mid-market UAE business“Leads go cold before anyone replies.”

The short answer

A Dubai tower's chiller contractor sends visit reports that say checked OK. What should a chiller maintenance report show, and when is the contractor's own report enough?

Pull the last three chiller visit reports and count the lines that are numbers. If they carry dated readings you can find in a minute, keep the contractor's report and file it against the chiller. If they say checked OK, write the readings into the contract and record them on the job. At Mindcat, we decide by that count.

A clipboard of ticks beside a tablet with a rising line, by a rooftop chiller in Dubai, under the words Ticks, or readings?

Takeaways

  1. 01Pull the last three chiller reports and count numbers against ticks. That count decides what happens next.
  2. 02A visit report should carry chilled and condenser water temperatures, pressures, approach, compressor amps and oil readings.
  3. 03Ticks cannot show a trend. A rising condenser approach over three visits can.
  4. 04Dubai Municipality's Legionella guideline asks for cooling water inspection and test records to be available for inspection and submitted every two weeks.
  5. 05One chiller, one contractor, dated reports with readings you can find in a minute: their report is enough.

If your chiller contractor's visit report says "checked OK" and nobody can find last summer's readings, this is for you. It is not for a building with one chiller and a contractor that already emails dated reports with readings.

The question usually comes after a trip. The chiller tripped twice in a hot week, the owners ask what the contractor found on the last service, and the answer is a sheet of ticks. Before the chiller maintenance contract renews, we run one test.

Can anyone read out last July's readings?

Ask your supervisor to open last July's chiller visit and read out three numbers: the leaving chilled-water temperature, the condenser approach and the compressor amps. Give them a minute.

Then pull the last three visit reports and count two things on each one:

  1. Lines that are numbers. A temperature, a pressure, amps, kilograms of refrigerant added.
  2. Lines that are ticks. "OK", "checked", "satisfactory", a box with a mark in it.
VisitNumbersTicksFound in a minute?
April014
July311
October014

The numbers in the table are a sample to show the shape of the count. Put your own three visits in their place. If the supervisor could not read out the three numbers, the count has already told you most of what you need.

Two sample reports of the same chiller visit: one with four OK ticks, one with four readings that can be compared
Same visit, two reports. Sample data.
To see a chiller job with its readings typed on the technician's phone, and the chiller's history a supervisor opens next July, see Mindcat Maintain, with real screens and sample data.

What should a chiller visit report show?

Numbers you can put next to last visit's numbers. A Dubai contractor's chiller checklist for 2026 puts it plainly for the quarterly service: "This is the contractor's visit. Each item should end up as a number on the report, not just a tick."

Its daily log, the sheet the site team keeps between visits, lists the readings worth asking the contractor to record as well:

ReadingWhat it tells you
Chilled water, entering and leavingLoad, and whether the chiller holds its setpoint
Condenser water, entering and leaving (outdoor air on air-cooled plant)How well heat is being rejected
Suction and discharge pressure, per circuitRefrigerant charge and heat-exchanger condition
Evaporator and condenser approachFouling, low charge, air in the circuit
Compressor amps or percentage loadMotor condition and capacity
Oil pressure, level and temperatureCompressor lubrication
Alarms since the last reading, run hours per compressorTrips, and duty rotation between compressors

For the quarterly visit the same checklist adds superheat and subcooling for each circuit against the nameplate, a refrigerant leak test, compressor amps and voltage balance, and safety devices trip-tested. Your chiller's own manual sets the intervals. Where the manual and a checklist differ, follow the manual.

Six readings to ask for: chilled water, condenser water, pressures, approach, compressor amps, oil pressure and level
The readings to ask for on every visit.

Why do ticks fail you next summer?

A tick says the technician looked. It cannot say whether the chiller is getting worse.

The same checklist names five log trends that mean call an engineer. The first is a rising condenser approach, which points to fouled or scaled tubes or air in the circuit. It quotes Trane's estimate that a 1°C rise in condenser temperature adds about 2 percent to operating costs. You can only see a rise across visits if each visit wrote the number down.

The US maintenance standard for commercial HVAC, ANSI/ASHRAE/ACCA Standard 180, builds its whole schedule on that comparison. When an unacceptable condition shows up on two successive inspections, the owner investigates the cause, starting with the technician's documentation. After three successive acceptable inspections, the frequency may be reduced, and the reason is documented. It also makes the building owner responsible for the programme, even when a contractor does the work. Standard 180 is not a UAE rule, but its logic holds anywhere: without numbers, you can neither catch a decline nor earn a longer interval.

A sample line of condenser approach rising from January to October, with the rule: rising means call an engineer
A trend only exists when the report has numbers. Sample trend.

Contractors say the same about their own trade. A commercial HVAC firm's guide to auditing your vendor warns that reports which are "checklists with everything marked 'okay' and no actual numbers" leave you "no way to verify the work or track trends over time". Another notes that "many facility managers receive generic service reports that say little more than 'system checked'".

What does Dubai already ask you to keep?

On a water-cooled plant, part of the chiller's record is not optional. Dubai Municipality's Technical Guidelines for Legionella Control in Water System (DM-HSD-GU44-LCWS2, version 6, issued 19 August 2025) say:

  • Cooling water systems, with their tanks, pumps, pipes and filters, are emptied, cleaned and disinfected at least once every six months, and whenever Legionella is detected.
  • A competent person tests the system for total bacteria count at least every month, and inspects the water treatment monthly.
  • Daily water treatment readings are kept and checked by the manager.
  • Inspection, maintenance and test records are available for inspection by Dubai Municipality staff and submitted every two weeks to its inspection address.

Dubai's green building system, Al Sa'fat (406.01), adds that test results are recorded and kept at site with the records of maintenance and remedial works. Confirm with Dubai Municipality how the guideline applies to your building before you rely on any interval here.

So the water results already have to sit with the maintenance records. The simplest place for the chiller visit reports is the same file.

One file per chiller: contractor reports, daily log, water treatment and Legionella results, oil analysis, refrigerant
What belongs in the chiller's file.

How we decide: their report, or your record

Our rule: pull the last three chiller visit reports and count numbers against ticks. If the reports carry dated readings and your supervisor can find last July's in a minute, keep the contractor's report and file it against the chiller. If they say checked OK, or they sit in someone's inbox, put the readings in the contract and on the chiller's own job record, entered at the plant.

  1. 01Pull the last three chiller visit reports.
  2. 02Count the lines that are numbers and the lines that are ticks.
  3. 03Ask the supervisor to find last July's leaving chilled-water temperature, condenser approach and compressor amps in a minute.
  4. 04Readings, and found in a minute: keep the contractor's report. Ticks, or lost in an inbox: readings go on the job.
What you findWhat we tell you
One chiller, one contractor, dated reports with readings, found in a minuteKeep their report. File each one against the chiller and stop there.
Readings on the report, but the report lives in an inbox or a scanKeep their report, and type the key readings onto the chiller's job so next July can compare them.
Ticks and "checked OK"List the readings in the contract before it renews, and record them on the job at the plant.
Several chillers or several contractors, each with its own formatOne record per chiller on your system, whoever does the visit.
Four steps: pull three reports, count numbers against ticks, find last July in a minute, then keep or record
How we decide: their report, or your own record.

The contract is the cheaper fix, and it comes first. A contractor that is told which readings to record usually records them. If the contractor will not add them before the renewal, have your own technician take the six readings at the next visit and put them on the job. The record on your side matters when you need to compare across visits, across contractors, or after the contract changes hands. A Gulf FM software vendor puts the test well in its guide to proof of work: if the contractor's monthly report cannot be rebuilt from the job records, it is not evidence.

Who holds which record across the fire, lift and chiller contractors is a wider question. Our post on whose system should hold the AMC reports works through it. When the visit dates themselves slip, start with the PPM calendar.

A rooftop chiller plant on a Dubai tower at sunrise, with gauges, insulated pipework and a phone on the railing
Where the readings start: the plant room, not the inbox.

What Mindcat Maintain keeps on the chiller

The readings, on the chiller's job, typed at the plant. In Mindcat Maintain each job carries its own checklist: values such as discharge pressure or leaving water temperature, pass or fail checks, and notes. The technician fills it in on a phone, whoever does the visit: your own team, or the AMC contractor's technicians, who get their own logins. Preventive schedules raise the monthly or quarterly chiller job on its date, and each chiller keeps its jobs, parts and meters. When the same chiller trips next July, the supervisor opens last summer's readings instead of asking who was on shift. A trip reported by a tenant becomes a job on that chiller too, and WhatsApp requests join once we connect your WhatsApp Business account during setup. That is the method we call "Complaint to closed job": every complaint or scheduled visit ends as a closed job with its readings.

Mindcat Maintain checklist with sample data: discharge pressure 21.4 bar, chilled water leaving 9.8°C, coils cleaned
A real Mindcat Maintain screen with sample data: the readings sit on the chiller job.

The readings are typed by the technician. Maintain does not read the chiller's controller or the BMS, and it does not set service intervals: those come from the manufacturer's manual and your contract. Attaching the contractor's PDF report, the water test results or photos to a job needs the maker's feature licence, which we bill at cost.

Maintain holds the building's plant, chillers, lifts and pumps, and the jobs technicians do on them. The laptops, phones and licences your staff hold belong in Mindcat Assets. Our facilities management page shows the FM setup with sample data.

Who should not start here?

A building with one chiller and a contractor that already emails dated reports with readings. File the reports against the chiller and spend the money elsewhere. And a building with no maintenance routine yet: Maintain runs the schedules from your AMC calendars, it does not write them.

What does it cost?

From the live Maintain page. The price is per technician a month, graduated: technicians 1 to 10 cost AED/SAR 149 each, 11 to 30 cost AED/SAR 99, 31 to 100 cost AED/SAR 69, and 101 and up cost AED/SAR 49, each band applying only to the technicians inside it. Requesters such as tenants and staff who only raise requests are free.

Every plan has a monthly minimum. The shared plan, up to 10 technicians, has a minimum of AED/SAR 2,649 a month. Your own copy hosted by us in the UAE or Saudi Arabia has a minimum of AED/SAR 5,699. The page's worked example: 30 technicians and supervisors come to 10 × 149 + 20 × 99 = AED 3,470, so the firm pays the AED 5,699 minimum, which covers up to 62 technicians.

The maker's feature licence (photos and files on jobs, the request portal, the PM calendar, vendors and more than 5 users) is billed at cost, at USD 15 per technician a month at its list price. For 30 technicians that is about USD 450 a month. The quick start, which we set up for you on the shared plan up to 10 technicians with our PPM schedule template for chillers, lifts, pumps, tanks and fan coil units, is AED/SAR 2,500, fixed. Larger teams get managed setup to a written plan. Prices exclude 5% UAE VAT and 15% Saudi VAT.

So a building team of up to 10 technicians on the shared plan pays the AED/SAR 2,649 monthly minimum, plus the maker's licence at cost.

Set that against the next chiller trip you cannot explain to the owners. Tell us how many technicians you run, which buildings they cover and how complaints reach them today. We reply with the setup plan and the monthly price per technician, in AED or SAR.

Filed under

Building maintenance and CMMS (Mindcat Maintain)chiller servicingchiller maintenance checklistchiller service report
Useful to someone on your team?

FAQ

Questions teams ask next

What should a chiller maintenance report include?
Numbers, not ticks. A Dubai contractor's 2026 checklist lists chilled-water entering and leaving temperature, condenser-water temperatures, suction and discharge pressure per circuit, evaporator and condenser approach, oil pressure and level, compressor amps, alarms since the last reading and run hours. For the quarterly visit it adds superheat and subcooling per circuit, a leak test and safety devices trip-tested. Each item should be a number on the report.
How often must a cooling tower be cleaned in Dubai?
Dubai Municipality's Technical Guidelines for Legionella Control in Water System (DM-HSD-GU44-LCWS2, version 6, issued 19 August 2025) say cooling water systems, with their tanks, pumps, pipes and filters, must be emptied, cleaned and disinfected at least once every six months, and when Legionella is detected. It also asks for a monthly total bacteria count by a competent person. Confirm with Dubai Municipality how the guideline applies to your building.
When is the chiller contractor's own report enough?
When you run one chiller with one contractor, and the contractor already sends dated reports with readings that your supervisor can find in a minute. File each report against the chiller and stop there. A system earns its place when the reports say checked OK, sit in someone's inbox, or come from more than one firm.
Does Mindcat Maintain read the chiller's controller or the BMS?
No. The technician types the readings into the checklist on the job, on a phone. Preventive schedules raise the chiller job on its date, and each chiller keeps its job history. Attaching the contractor's PDF report or photos to a job needs the maker's feature licence, billed at cost.

Sources

  1. 01Samra Fitout: Chiller Maintenance Checklist for Dubai Buildings 2026 (1 October 2026)Accessed 18 Nov 2026
  2. 02Dubai Municipality: Technical Guidelines for Legionella Control in Water System, DM-HSD-GU44-LCWS2, V6, 19 August 2025Accessed 18 Nov 2026
  3. 03Dubai Municipality: Dubai Green Building System (Al Sa'fat), 406.01 Legionella Bacteria and Building Water SystemsAccessed 18 Nov 2026
  4. 04ANSI/ASHRAE/ACCA Standard 180-2012, sample pages (sections 4.2.2.d and 4.2.2.e)Accessed 18 Nov 2026
  5. 05CG Service Pros: How to Audit Your Current HVAC Vendor Without Burning the Relationship (17 February 2026)Accessed 18 Nov 2026
  6. 06Tom's Commercial: The Hidden Risks of All-In-One Bundled Service Contracts for HVAC Maintenance (13 August 2025)Accessed 18 Nov 2026
  7. 07Lattice Gulf: Technician Proof of Work in FM (30 October 2026)Accessed 18 Nov 2026
  8. 08Mindcat Maintain: checklists with readings, preventive schedules, the maker's licence, prices (live page)Accessed 18 Nov 2026
Shivanath Devinarayanan, founder of Mindcat

Written by

Shivanath Devinarayanan

Founder, Mindcat Consulting · Salesforce MVP Hall of Fame

Builds and runs AI agents in production. Reads every brief that comes in and signs the work that goes out.

About Shivanath

Mindcat Maintain · the written assessment

We work in real estate and right now, leads go cold before anyone replies.

Industry
Problem

Brief: Real estate. Leads from portals and WhatsApp. Follow-up has no owner. An agent on a named process. A reviewer on the exceptions. From: /blog/chiller-maintenance-report-readings-or-ticks.